Granny Flat: Elemental Deemed to Satisfy

Created by Vicki Marshall, Modified on Tue, 15 Nov 2022 at 11:16 AM by Vicki Marshall


Region: All States

 

Assessor Question:


I'm chasing some clarification regarding a new dwelling I'm providing an energy rating report for.

 

There is a proposed separate bedsit/granny flat on the property that is not connected to the main building. It consists of a rumpus, store room, bedroom, ensuite & WIR. (no kitchen)

 

Is it your expectation that a separate energy rating is completed for this proposed building?


TechLink Response:


  • NatHERS software cannot be used because the proposed granny flat has no kitchen.
  •  The alternative approaches in this case are Elemental Deemed to Satisfy or Performance Solution.
  • The two Deemed to Satisfy pathways in NCC vol 2 for Class 1a dwellings, being main wings with a kitchen or satellite wings without a kitchen, are Elemental DtS and NatHERS DtS. 
  • The Elemental DtS approach is less flexible than a NatHERS DtS assessment due to the inability to balance under performance of any element against over performance of another.
  • If the DtS approaches are unsuitable for some reason it is possible to use a Performance Solution or Expert Opinion to confirm that a design exceeds or is at least equal to the result that would achieve regulatory compliance with one of the two DtS methods.
  • The ABCB provides good guidance as to what is required for non-DtS methods to give a Building Surveyor/Certifier confidence that the design achieves a suitable level of performance.
    https://www.abcb.gov.au/resource/infographic/performance-solution-process-overview

Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select atleast one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article